As a device for ventilation and air supply, fans sometimes require insulation for the conveyed air.
For instance, when supplying hot air, if there is a significant temperature difference between the fan’s operating environment and the medium it conveys, the medium temperature can drop, gas density increases, and the required power rises, potentially causing the original motor to overload.
To maintain the medium temperature unaffected by the ambient temperature, it is usually necessary to install an insulation layer on the fan surface. Insulation also helps reduce noise and prevent burns.
1.Core Objectives of Insulation
Preventing Motor Overload (Primary Process Objective): For hot air fans, if heat dissipation causes the gas temperature to drop and density to increase, the actual work performed by the fan will increase (required power is proportional to gas density), potentially causing the originally selected motor to operate under overload. Insulation is a key measure to ensure the system operates stably under design conditions.
Ensuring Process Temperature Requirements: In processes requiring the conveyance of gases at specific temperatures (e.g., drying, heating reactions), insulation ensures the medium meets the required temperature upon reaching the point of use.
Reducing Energy Loss: Insulation minimizes heat (or cooling) loss during conveyance, lowering energy costs.
Preventing Burns: It prevents the external shell temperature from becoming too high, avoiding burns to personnel.
Noise Reduction: The insulation layer (especially flexible materials like rock wool) can provide some sound absorption and noise insulation.

2.Conventional Insulation Structure and Its Limitations
The conventional insulation method involves directly welding metal insulation brackets (typically made from angle steel or flat steel) onto the fan casing, then covering the brackets externally with insulation material (such as rock wool boards/blankets) and a metal protective layer (such as galvanised iron sheet or aluminium sheet).
Metal brackets are excellent thermal conductors. They form a direct connection between the high-temperature casing and the external environment, creating a pathway for rapid heat loss.
At ambient temperatures or where temperature differentials are minimal, the primary thermal insulation provided by the insulation material masks this ‘thermal bridge’ effect, yielding acceptable overall insulation performance.
However, under extreme conditions of high temperatures (e.g., >250°C) or low temperatures (e.g., <0°C), heat loss through the ‘thermal bridge’ becomes highly significant, leading to:
① Excessively high/low localised outer wall temperatures: Even with insulation, the temperature at the external location corresponding to the metal bracket may significantly exceed or fall below ambient temperature;
② Inability to meet stringent temperature differential requirements: Achieving the stipulated ‘50°C temperature difference between the external surface and the fan’s internal temperature’ becomes challenging. Here, ‘external temperature’ should be understood as the temperature on the outer surface of the fan’s insulation layer.

3.Optimized Solutions for Non-Standard Temperature Conditions
Filling the metal insulation supports with insulation material, i.e., rock wool, is the core optimization measure to address the “thermal bridge” problem.
This is referred to as a “broken thermal bridge” or “thermal break spacer” design.
A complete optimized solution typically includes:
(1) Optimized Support Design
Filling Cavities:Tightly fill the cavities of the supports welded to the casing with high-temperature-resistant rock wool or ceramic fiber wool to block the heat transfer path through the internal air and the metal itself of the support.
Adding Thermal Break Spacers: Add a spacer made of insulating material (e.g., ceramic fiber pad, high-temperature rubber pad) between the metal support and the casing to physically break the direct metal-to-metal contact. This is a more thorough approach.
Optimizing Support Geometry:Use narrow and tall support designs, where structural strength is ensured, to reduce the cross-sectional area for heat conduction.
(2) Selecting Appropriate Insulation Materials
High-Temperature Applications:Must use high-temperature resistant insulation materials, such as ceramic fiber wool/blanket, aluminum silicate fiber wool, etc., which can withstand temperatures up to 1000°C and above.
Standard rock wool typically has a long-term temperature resistance around 600°C; selection should be based on the specific temperature.
Low-Temperature/Cold Insulation Applications:Require cold insulation materials with high closed-cell content, such as foam glass, polyurethane foam (PUR/PIR), etc., to prevent moisture ingress and freezing.
Determining Optimal Thickness:Under extreme temperature differences, relying solely on conventional thicknesses (e.g., 50-100mm) of insulation is insufficient.
It is necessary to determine the optimal insulation thickness, balanced between economic cost and minimal heat loss, through thermal calculations. Sometimes, 150mm or even greater thickness may be required.